Pioneer™ 16R Model

Pioneer™ 16R Model
Производитель: RKI Instruments
Модель: Pioneer_16R
Запросить цену
Описание

Features

Industry Applications

  • Simultaneous readout of 16 channels
  • 3 alarm levels per channel
  • Zero correction and stabilizing
  • software eliminates sensor drift
  • Discrete and common programmable
  • relays
  • 4-20 mA outputs
  • Receives a wide variety of sensors
  • Accepts any 4-20 mA transmitter input
  • powered from 24 VDC
  • Input voltages: 115 / 220 VAC or 12 VDC
  • Form C, 8 Amp rated relays
  • Standard 19” rack mount
  • Petrochemical plants
  • Refineries
  • Water & wastewater treatment plants
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive
  • HVAC

 

The Pioneer™ 16R is a 19” rack mounted version of our popular Pioneer™ series of gas monitors.
This continuous monitoring controller is capable of handling up to 16 separate sensor inputs to detect gas levels from 1 to 16 remote locations. The 4 display screens on the front panel simultaneously displays the gas level for all active channels.
The Pioneer 16R includes three programmable alarm levels per channel, as well as audible and visual alarms which warn you of hazardous gas conditions. Versatile standardized plug-in cards allow a wide variety of inputs and outputs.

Physical

Dimensions

Height 6.9” 175mm
Width 19.0” 483mm
Depth 12.0” 305mm

Enclosure

Standard 19” rack mount

Wiring Termination

Screw type terminal block 12 gauge max.

Environmental

Operating Temp

32°F to 122°F (0°C to 50°C)

Storage Temp

-4°F to 158°F (-20°C to 70°C)

Relative Humidity

0 - 95% RH non-condensing

Inputs

Direct Wired Sensors

LEL / PPM Hydrocarbon, Oxygen
Remote amp not required for less than 500 feet.

4-20 mA

Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire, 250 mA max standard). A wide variety of RKI/Riken sensors are available with 4-20 mA signals (see List Of Detectable Gases).
Wiring distances up to 5,000 feet.

Zero Correction

Zero correction and stabilizing software effectively eliminates all reasonable sensor drift.

Sampling Methods

Diffusion and sample draw heads available.

Outputs

Relays

3 relays per channel - (Alarm 1, Alarm 2, Alarm 3 or Fail)
4 common relays - (Alarm 1, Alarm 2, Alarm 3, Fail)
Single pole, double throw (SPDT) isolated contacts
Rated - 250 VAC to 8A
Individual Relay Settings: increasing or decreasing
Global Relay Settings: latching or self reset normally energized or normally de-energized time delay for alarm on and alarm off.

4-20 mA

Separate current or voltage outputs for each of the 16 channels; non-isolated, 4-20 mA (into 500 ohms impedance max).

0 - 1 VDC

Optional 0 to 1 VDC (into 200 ohms impedance min).

24 VDC

24 VDC output provided to operate sample drawing adapters.

Display

4 alphanumeric displays with backlighting. 20 characters per line, 4 lines each (16 lines total).

Audible

Internal mounted buzzer, 94 db. Coded output
Pulsing = Gas Alarm
Steady = Fail

Visual

5 color coded LED's: Alarm 1, Alarm 2, Alarm 3, Pilot, and Fail.

Power

115 VAC or 12 VDC
Optional - 230 VAC
Battery Backup option available

Controls

5 front mounted push buttons for setup and programming.

Warranty

One year materials and workmanship.